Do you want to save money on energy bills? Then contact Ronfell on +44 (0) 1257471060
Open
X

2G. Corridor with passive IR detector

Dimmable HF ballasts, soft start and multi-level “Dynamic Lighting control”

Premises

This application shows a hotel corridor with doors on one side and windows that allow plenty of natural light to enter on the other side. It is used very frequently during certain times of the day, when people pass through often. A dynamic daylight-regulated lighting system is therefore installed.

Light source

The light fittings in this application have dimmable HF ballasts with 1 – 10 V control.

Placement of detectors and lens choice

To achieve optimum detection and a high level of comfort it is important for detectors to be mounted in the correct position. This is particularly important with corridor solutions. Unfortunately one far too often sees detectors aimed at doors and entrances, thus adversely affecting detection.

The optimum detection direction is obtained when people pass across the detection field at 90°, and the worst detection accuracy is obtained when people walk towards or away from the detection field. For this reason the detector should be fitted with a lens that provides a 90° detection angle. It should be installed in a corner next to the door that most people pass through, so that it is not obscured when the door is opened. The correct installation height is 1.6–1.9 m in corridors.

In corridors up to 40 m long a number 15 standard lens is suitable. Long corridors require a lens that combines a long field of view and a 90° angle of view, such as lens 41. In long corridors that have an entrance door at the far end, detection may be poor when people enter through this door. This is because there is little movement across the field of view. There are around 40 other lenses to choose from. See the lens archive in the handbook.
See also alternative ceiling mounting in application 2F!

Control system

With new buildings or renovations, when there is a possibility of selecting fittings with dimmable operating devices, installation should be in accordance with the principle of ‘Dynamic Lighting Control’. The technology can be used for control using both acoustic and IR detectors. See wiring diagram below. With the NV-4T, dimmable fluorescent-tube fittings can provide control on four light levels.

The most important advantages attained using Dynamic Control are as follows:

  • Evenly distributed basic light without extra fittings, operating at a level of 100 per cent.
  • The possibility of saving 20 – 25 per cent during operation.
  • Lower working temperature in the fittings, resulting in a lower life.
  • Fewer activations and less power supplied, reducing wear on the fluorescent powder and resulting in a longer life of the light sources.
  • The possibility of avoiding adherence to the light-source manufacturers’ recommendations regarding burning times, thus drastically reducing the operating times and increasing the saving.

During the day, when there is sufficient natural light, the light sensor in the PD-2200 prevents the lighting from being switched on at all. It is adjusted to the desired level so that the lighting is switched on when presence is detected.
When there is insufficient natural light the lighting is switched on automatically when presence is detected by PD-2200. An external light sensor, LS-10, switches NV-4T between a daytime programme and a nighttime programme.
In the morning or afternoon when there is insufficient natural light, the lighting is switched to 80 per cent when presence is detected.
When presence is no longer detected during the day, the lighting is first reduced to the 15 per cent comfort level, and if no presence is detected for 1–2 hours the lighting is switched off entirely to eliminate idle losses.

After dusk the system switches to the nighttime programme and the lighting is switched to around 30 per cent of the level used when presence is detected.

When presence is no longer detected at night the lighting is first reduced to around one per cent base lighting, and after around 1–2 hours the lighting is switched off entirely to eliminate idle losses.

When switching from a low level to a higher level the lighting is always ramped up gradually by the SD-1 soft dim module. The ramp-up rate can be adjusted by means of a potentiometer. The ramp-down rate cannot be adjusted. See the graph on the right.

The energy saving is around 20 per cent during daytime operation and around 70 per cent during the evening and at night when the lighting is switched on.
See the diagram below!

Installation of the detectors should be using the simplest possible cable, Type EKKX 1 x 4 x 0.25 mm2. All detectors should be connected in parallel with the rectifier EXE-2000, even if they form part of different areas. Regarding adjustment of the IR detectors one is referred to the manual enclosed with the detector.

Product Order No.
IR detector PD-2200 13140
Rectifier EXE-2000 18108
Level selector NV-4T 13171
Soft start module SD-1 13173
Light sensor 13100
Lens 17 13031 + lens No.
Product Maximum current consumption (mA)
IR detector
PD-2200
25
Level selector NV-4T 110
Soft start module SD-1 35
Daylight-dependent lighting control with NV-4T in corridor